Hardware + software · ready-made package with installation

Clean water, automatically and safely

The Ultimate Reverse Osmosis Controller runs reverse osmosis units. It starts and stops production on its own based on the tank level and flushes the membrane before every cycle. It monitors pressures, TDS, pH, flows, temperatures and frost, and stops the pump as soon as something is not safe. You operate it from a 7" touch screen on the panel and from your browser, over Ethernet or WiFi.

  • 5 errorsstop the pump immediately
  • 11 warningsbefore a problem becomes a failure
  • 3 TDSfeed, product, waste
  • 0 cloudworks on your local network
The Live Status screen of the web interface: operating state, tank and sensors
The main page of the 7-inch touch screen
Web interface and 7" touch screen – the same data, at the same moment.

The whole R/O unit, under control

For hotels, restaurants, workshops, homes and any site that produces its own clean water. The controller does the work on its own and alerts you only when needed.

  • 3pressure sensors: feed, membrane, waste
  • 2flow meters for product water and waste
  • 11status lights on the panel
  • 1′logging of all measurements every minute

All features, in one box

In normal operation you don't need to do anything. The controller produces water when the tank needs it, protects the membrane and keeps a record of every litre.

Automatic cycle

Production starts when the tank drops to the lower limit (e.g. 80 %) and stops when it is full (e.g. 98 %). Hysteresis prevents constant restarts.

Membrane flush

A short membrane flush before every production run, plus manual FLUSH with one button.

Pressures & ΔP

Feed, membrane and waste pressure, plus the pressure drop across the membrane, which shows early that the membrane is starting to clog.

TDS & salt rejection

TDS at the feed, in the product water and in the waste, salt rejection rate and a check that the three sensors agree.

Flows & recovery

Product and waste flow in L/min and recovery rate: how much of the incoming water becomes clean water.

Tank in litres

Cylindrical or rectangular tank: enter the dimensions and see volume, capacity, height and fill percentage.

Tank pH

Continuous measurement with two-point calibration. Green within drinking-water limits (6.5–8.5), red outside them.

Frost & temperatures

Feed and tank water temperature, temperature and humidity inside the panel and in the room. The pump is locked out when there is a risk of frost.

R/O Standby

For periods without use: short scheduled runs, so that water does not stand still in the membranes.

UV-C disinfection

UV-C lamp with a season and a daily schedule that you set.

Statistics & filters

Litres and operating hours since the start, since the last filter change and since your own reset. Reference values at every filter change for comparison.

Logs in CSV

Every event, command and settings change with who made it, and all measurements every minute, in CSV files for Excel.

See the software

Real screens of the controller. Click an image to enlarge it.

7" touch screen

The status at a glance, right on the panel

The main page shows the operating state in colour (STANDBY, FLUSHING, PRODUCTION or fault), the active errors and warnings and the state of the inlet valve, the flush valve and the pump.

  • START, STOP and FLUSH with one touch
  • Alerts, Data & Statistics and Settings pages
  • Settings with −/+ that save themselves
The main page of the touch screen

Live Status

The whole unit on one browser page

Operating state with the control buttons, tank in litres and percent, TDS, salt rejection, pressures, membrane ΔP, flows, recovery and temperatures, refreshed every second.

  • From a computer, tablet or phone, over Ethernet or WiFi
  • Green values when everything is fine, red when not
  • All active errors and warnings, one below the other
The Live Status screen

Alerts & Troubleshooting

The controller explains what happened and what to do

For every error and warning, the touch screen and the web interface show what it means, the possible causes and the steps to fix it, together with the live values.

  • Audible alert with its own Morse “word” for every problem
  • Adjustable repeat or silencing of the buzzer
  • 11 status lights on the panel, even without a screen
The Alerts page

Settings

Limits, tank, Standby, UV-C, network

Settings are grouped in tabs, the same in the web interface and on the touch screen. The controller checks every value before saving it.

  • TDS, pressure, ΔP and salt rejection limits, flush duration
  • Tank dimensions and start / stop levels
  • pH calibration, Ethernet, WiFi, users, buzzer and SD card
The Settings screen

Data & Statistics

Litres, hours and reference values

How much water was produced and how many hours the unit ran, since the start, since the last filter change and since your own reset. At every filter change the controller stores the pressures and TDS as a reference point.

  • Comparison of current values with the reference values
  • Reset Count and Filters Replace with confirmation on the screen
The Data and Statistics page

Logs

Complete history on the microSD card

Every event, colour-coded by type: errors, state changes, commands, settings changes with the old and the new value, user logins and clock synchronisation.

  • Filter by type and browse previous months
  • Download as CSV for Excel with one button
  • Measurements every minute in separate monthly files
The Logs screen

More screens

Touch screen and web interface.

Protection for the membrane and the water

On every fault the controller stops the pump immediately and closes the valves. Serious faults stay locked until a person has looked at them.

Low pressure

The pump never runs without water: a pressure sensor plus an independent pressure switch. It recovers on its own once the pressure is restored.

Membrane overpressure

Above the safety limit the pump stops and the fault locks, until the cause has been found and fixed.

Bad water stays out of the tank

If the TDS of the product water exceeds the limit, production stops and locks, so the tank is not filled with poor-quality water.

Frost

Below 0 °C in the feed water or in the tank, operation locks and restarts on its own once it warms up.

Safety float

Independently of the level sensor, the high-level float stops production when the tank is full.

Sensor failure

If the water temperature sensor is lost, the pump stops, because without it frost cannot be ruled out.

No false alarms

Warnings appear only when the condition lasts a few seconds, and not during stabilisation after the pump starts.

Safe storage

Settings, counters and users in two alternating copies with a checksum. A power cut never destroys the last good copy.

The controller monitors water quality, but it does not replace the laboratory analyses required for drinking water. The electrical installation is carried out by a licensed electrician, with a 30 mA residual current device.

What the package includes

We deliver the controller assembled and programmed, together with the sensors, the screen and the documentation. It fits new or existing R/O units, and the final list is adapted to your installation.

Controller

  • Arduino DUE (ARM Cortex-M3, 32-bit)
  • Ethernet with microSD card
  • DS3231 clock with battery
  • Relays for valves, pump and UV-C
  • Buzzer and 11 LED indicators

Sensors

  • 3 pressure sensors and pressure switch
  • 3 TDS sensors
  • 2 flow meters
  • 4–20 mA level sensor and float
  • pH, 2 water thermometers, 2 temperature/humidity sensors

Operation

  • CrowPanel 7" touch screen
  • Web interface over Ethernet and WiFi
  • Admin and View users
  • On-screen keyboard and network scan

Software & documentation

  • Firmware FW1.0.18 for controller and screen
  • Screen update from a microSD card
  • User manual (PDF)
  • Pinout and wiring diagram

Wiring

Documented wiring, pin by pin

Every installation comes with the controller pinout and a complete wiring diagram for sensors, relays, indicators and communication modules.

  • All analogue inputs adapted to the controller's 3.3 V
  • Relays for inlet valve, flush valve, high-pressure pump and UV-C
  • Screen on a separate power supply, connected with two wires
Wiring diagram

Technical specifications

Firmware FW1.0.18.

ControllerArduino DUE – SAM3X8E, ARM Cortex-M3 32-bit, 3.3 V logic
Touch screenCrowPanel 7" ESP32-S3, 800 × 480, capacitive touch, WiFi 2.4 GHz
NetworkEthernet (static IP or DHCP) and WiFi through the screen, at the same time
Web interfaceLive Status, Statistics, Settings, Alerts, Logs, Help · refreshed every 1 s · up to 6 simultaneous users
UsersAdmin and View · up to 8 additional accounts · SHA-256 salted passwords · lockout after 3 failed attempts
PressuresFeed, membrane, waste, membrane ΔP · low-pressure switch
Water qualityFeed / product / waste TDS, salt rejection, recovery, tank pH with 2-point calibration
FlowProduct water and waste (L/min) · litre and hour counters
TankCylindrical or rectangular · 4–20 mA level · high-level float
TemperaturesFeed and tank water (DS18B20) · panel and room (DHT11)
OutputsInlet valve, flush valve, high-pressure pump, UV-C, buzzer, 11 LED indicators
Alerts5 errors, 11 warnings, Morse words on the buzzer, repeat every 1–10 minutes or silence
StoragemicroSD FAT32 up to 32 GB · settings, counters, users · events and per-minute measurements in CSV
ClockDS3231 with battery · NTP synchronisation

User manual

A detailed guide to every screen, setting, alert and maintenance task, with images from the web interface and the touch screen.

The cover of the user manual
PDF · English

Ultimate Reverse Osmosis Controller – User manual

For the owner, the staff and the maintenance technician.

  • Introduction, safety instructions and system parts
  • How it works: cycle, states, protections
  • The web interface: all screens and cards
  • The touch screen, Ethernet and WiFi
  • Errors, warnings, buzzer and LED indicators
  • Settings table with defaults
  • Maintenance, pH calibration, updates, troubleshooting
  • Pinout, wiring diagram and technical specifications
Version
Firmware FW1.0.18
Pages
52
Size
6.5 MB
Download the manual (PDF)

Frequently asked questions

Does it need the internet to work?

No. The controller works on its own and the touch screen always works. The web interface only needs the local network (Ethernet or WiFi). The internet is used only, if available, to synchronise the clock.

Will it fit my R/O unit?

The controller fits units with an inlet valve, a flush valve and a high-pressure pump, in new or existing installations. Send us the details of the unit and the tank for a quote.

Can I see it from my phone?

Yes, from any browser on the same network, through an Ethernet cable or WiFi. For remote access we recommend a VPN connection, because the web interface is not encrypted.

What happens if the power goes out?

Settings, counters, users and history are on the microSD card, in duplicate copies, and the time is kept by the battery-backed clock. When power returns, the controller starts with the saved settings and counters.

When should I change the filters or the membrane?

The controller keeps the pressures and TDS from the last filter change as a reference point. When the membrane pressure or ΔP rises, or the salt rejection drops, a warning appears before the unit reaches a failure.

The house or hotel closes for the winter. What do I do?

Enable R/O Standby for the period without use: the unit performs short runs on its own, so that water does not stand still in the membranes. If there is a risk of frost, the controller locks the pump.

How is the software updated?

The screen software is updated from a microSD card, without a computer: you put the file we give you on the card and switch the screen on. The controller and the screen must always have the same version.

Feature requests

Something missing? Suggest it.

Suggest any feature you consider essential in Ultimate Reverse Osmosis Controller. We will evaluate it and, if approved, add it to the next upgrade of the program, completely free of charge.

  1. You write to usDescribe what you need and how it would help your daily work.
  2. We evaluate itWe review it technically and functionally and let you know the outcome.
  3. It comes freeIf approved, it is included in the next upgrade at no extra cost.

Your suggestion goes straight to the development team. We use your details only to tell you the result of the evaluation.

Request a quote

Tell us a little about your R/O unit and your tank, and we will send you a quote for the package and the installation.

Athens (head office)

Kioutacheias 19, 162 31 Vyronas

Corfu

Dim. Odos Kato Agiou Markou, 490 83 Pyrgi

Email:

Your message goes straight to info@aenaonict.gr. We use your details only to reply to you.